Refrigerant Line: Replacement
- DISCHARGE REFRIGERANT FROM REFRIGERATION SYSTEM
- REPLACE FAULTY TUBE OR HOSE NOTE: Cap the open fittings immediately to keep moisture or dirt out of the system.
- TORQUE CONNECTIONS TO SPECIFIED TORQUE NOTE: Connections should not be torqued tighter than the specified torque.TORQUE SPECIFICATION TABLE
Part tightened N.m kgf.cm ft.lbf Condenser at Discharge tube 9.8 100 87 in..lbf Condenser at Liquid tube 9.8 100 87 in..lbf No. 1 suction Tube at Suction Tube 9.8 100 87 in.lbf Discharge tube at Discharge tube 9.8 100 87 in..lbf Discharge tube at Discharge tube (Washer Bolt) 22.1 225 16 Suction tube at Suction tube (Washer Bolt) 31.9 325 24 Compressor at Discharge hose 9.8 100 87 in..lbf Compressor at Suction hose 9.8 100 87 in..lbf Expansion valve at Evaporator 3.4 35 30 in..lbf - EVACUATE AIR IN REFRIGERATION SYSTEM AND CHARGE WITH REFRIGERANT
Specified amount: 500 +/- 30 g (17.64 +/- 1.06 oz.)
- INSPECT FOR LEAKAGE OF REFRIGERANT
Using a gas leak detector, check for leakage of refrigerant.
- INSPECT AIR CONDITIONING OPERATION