Test Reading
WARNING: This page is about a different car, the 2008 Nissan Quest. However, it is still accessible from the selected car via links, so may be relevant.
RECIRCULATING-TO-DISCHARGE AIR TEMPERATURE TABLE
| Inside air (Recirculating air) at blower assembly inlet | Discharge air temperature at center ventilator °C (°F) | |
|---|---|---|
| Relative humidity % | Air temperature °C (°F) | |
| 50-70 | 25 (77) | 9.7 - 13.7 (49 - 57) |
| 30 (86) | 12.6 - 16.6 (55 - 62) | |
| 35 (95) | 14.9 - 19.9 (59 - 68) | |
| 40 (104) | 17.3 - 23.3 (63 - 74) | |
AMBIENT AIR TEMPERATURE-TO-OPERATING PRESSURE TABLE
| Ambient air | High-pressure (Discharge side) kPa (kg/cm2 , psi) | Low-pressure (Suction side) kPa (kg/cm2 , psi) | |
|---|---|---|---|
| Relative humidity% | Air temperature °C (°F) | ||
| 50-70 | 25 (77) | 1,059 - 1,294 (10.8 - 13.2, 153.6 - 187.7) | 216 - 255 (2.2 - 2.6, 31.3 - 37.0) |
| 30 (86) | 1,206 - 1,481 (12.3 - 15.1, 174.9 - 214.8) | 255 - 304 (2.6 - 3.1, 37.0 - 44.1) | |
| 35 (95) | 1,393 - 1,706 (14.2 - 17.4, 202.0 - 247.5) | 275 - 343 (2.8 - 3.5, 39.8 - 49.8) | |
| 40 (104) | 1,510 - 1,844 (15.4 - 18.8, 219.0 - 267.4) | 343 - 422 (3.5 - 4.3, 49.8 - 61.2) | |