Refrigerant Charging: Evacuation

  1. Open all the valves of the manifold gauge.
    CAUTION:
    • Close the manifold gauge valve immediately after stopping the vacuum pump. If the valve is left open, the vacuum pump oil will back flow into the refrigeration cycle and cause a decrease in the efficiency of the air conditioner.
  2. Start the vacuum pump and let it operate for 15 min  .
    Fig 1: Closing Low-Pressure Side Valve Of Manifold Gauge
    G09075740Courtesy of MAZDA MOTORS CORP.
  3. Verify that high- and low-pressure side readings of the manifold gauge are at -101 kPa {-1.03 kgf/cm 2  , -14.6 psi}  . Close each valve of the manifold gauge.
    Fig 2: Checking High And Low Pressure Side Readings Of Manifold Gauge
    G09075741Courtesy of MAZDA MOTORS CORP.