Test Reading

WARNING: This page is about a different variant/trim than selected.
RECIRCULATING-TO-DISCHARGE AIR TEMPERATURE TABLE

Inside air (Recirculating air) at blower assembly inlet Discharge air temperature at center ventilator °C (°F)
Relative humidity % Air temperature °C (°F)
50 - 60 20 (68) 6.3 - 7.9 (43 - 46)
25 (77) 10.6 - 12.8 (51 - 55)
30 (86) 14.8 - 17.6 (59 - 64)
35 (95) 19.0 - 22.3 (66 - 72)
60 - 70 20 (68) 7.9 - 9.4 (46 - 49)
25 (77) 12.8 - 14.9 (55 - 59)
30 (86) 17.6 - 20.3 (64 - 69)
35 (95) 22.3 - 25.7 (72 - 78)
AMBIENT AIR TEMPERATURE-TO-OPERATING PRESSURE TABLE

Ambient air High-pressure (Discharge side) kPa (kg/cm2 , psi) Low-pressure (Suction side) kPa (kg/cm2 , psi)
Relative humidity % Air temperature °C (°F)
50 - 70 20 (68) 768 - 940 (7.8 - 9.6, 111.4 - 136.3) 180 - 220 (1.8 - 2.2, 26.1 - 31.9)
25 (77) 925 - 1, 131 (9.4 - 11.5, 134.1 - 164.0) 218 - 267 (2.2 - 2.7, 31.6 - 38.7)
30 (86) 1, 082 - 1, 322 (11.0 - 13.5, 156.9 - 191.7) 258 - 314 (2.6 - 3.2, 37.4 - 45.5)
35 (95) 1, 238 - 1, 513 (12.6 - 15.4, 179.5 - 219.4) 296 - 362 (3.0 - 3.7, 42.9 - 52.5)
40 (104) 1, 395 - 1, 704 (14.2 - 17.4, 202.3 - 247.1) 335 - 408 (3.4 - 4.2, 48.6 - 59.2)