Repair Procedures: Replacement
WARNING: This page is about a different variant/trim than selected.
- Discharge refrigerant from refrigeration system.
- Replace faulty tube or hose.CAUTION: Cap the open fittings immediately to keep moisture or dirt out of the system.
- Tighten joint of bolt or nut to specified torque.CAUTION: Connections should not be torque tighter than the specified torque.TIGHTENING TORQUE CHART
Part tightened N.m kgf.m lb-ft Condenser - Discharge hose 4.9~5.9 0.5~0.6 3.6~4.3 Condenser - Liquid tube Compressor - Discharge hose 4.9~5.9 0.5~0.6 3.6~4.3 Compressor - Suction hose Expansion valve - Evaporator 11.8~14.7 1.2~1.5 8.7~10.9 - Evacuate air in refrigeration system and charge system with refrigerant.
Specified amount : 19.4 ± 0.88 oz. (550 ± 25g)
- Inspect for leakage of refrigerant.
Using a gas leak detector, check for leakage of refrigerant.
- Inspect A/C operation.