Refrigeration Diagnosis Chart
Observe refrigeration system in areas listed below while engine operates at 2, 000 RPM with control lever in "HI" and temperature dial at 65. Blower motor should be disconnected when required in chart.
| System Defect | Outlet Air Temp. (in "HI") | Sight Glass | Head Pressure At Ambient Temperature | Evaporator Pressure | Evaporator Outlet Pipe (Ahead of STV) | Oil Bleed Line | System Correction | |||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| -No Defect- Normal |
40-50° | Clear | Temperature | 29-32 P.S.I. | Cold | Warm | ||||||||
| Bubbly with blower off | 70 | 80 | 90 | 100 | Maintains press with blower disconnected | Gets cold with blower disconnected | ||||||||
| 160 200 |
190 230 |
220 260 |
250 290 |
|||||||||||
| Low Charge (1) | Warm | Foamy or Bubbly | Low | Normal to Low | Warm | Cold | Find and repair leak. Recharge | |||||||
| Lost Charge (1) | Warm | Clear | Very low | Very low | Warm | Warm | Find and repair leak. Recharge | |||||||
| Expansion (1) valve inlet screen(2) plugged | Warm | Clear | Low | Low | Warm | Warm | Replace X-valve | |||||||
| Capillary (2) broken (Valve (1) Closed). | Goes to vacuum with blower disconnected | Cold-Equalizer line also cold | Clean or replace inlet screen | |||||||||||
| Capillary bulb-poor contact to pipe or bad insulation | Normal to Warm | Clear | Normal | High | Cold to Cool | Warm | Reclamp bulb at 3 o'clock location. Replace insulation | |||||||
| Suction throttling valve-setting too high | Warm | Clear | Normal | High | Cool to Warm | Cold at low Ambient temp Warm at high Ambient temp | Replace STV | |||||||
| Won't pull down with blower disconnected | ||||||||||||||
| STV-Shut due(1) to loss of (2) bellows vacuum or binds shut | Warm | Foamy to Bubbly | Normal | High | Warm | Warm | Replace STV (Note: car with this defect will not take full charge) | |||||||
| Equalizer Line cold | ||||||||||||||
| STV-Stuck (1) Open | Cold | Clear | Low | High or Low | Cold | Warm | Replace STV | |||||||
| May lose air flow on humid days | Goes to vacuum with blower disconnected | |||||||||||||
| Restriction in (1) receiver (Liquid line cold) | Warm | Bubbly | Low | Low | Cool or Warm | Cool or Warm | Replace receiver dehydrator | |||||||
| Over charge (blows relief valve on hot days) | Normal | Clear | High | Normal | Cold | Warm | Recharge to specification | |||||||
|
||||||||||||||